Executive Summary of Operations
Inframark submitted the April 2026 monthly report for the Ebensburg wastewater treatment facility. Key operational statistics and maintenance activities included:
- Wastewater Volume: The plant treated a total of 25,542,200 gallons, averaging 851,406 gallons per day.
- Sludge Management: The centrifuge was operated weekly, resulting in 11. 67 tons of dry sludge sent to the landfill.
- Equipment Repairs:
- Process Water Pump #2: Rebuilt with new bearings, mechanical seals, shaft sleeve, and wear rings. Motor bearings were also replaced and load tested.
- UV System: Annual maintenance was performed on the Trojan UV-A side bank (new wipers and fluid installed). A leaking coolant fitting was identified as the root cause of gradual coolant loss; repairs have stabilized levels.
- Centrifuge PLC: The battery died and was replaced; alarms were cleared.
- SBR #2 Air Valve: An actuator motor failure was resolved by installing a spare motor.
- Blower Room: Belts were replaced on the exhaust fan.
- Infrastructure Improvements: Old wiring in the basement was terminated and cleaned where equipment was no longer present. New plumbing was installed for the screw pump water chase, eliminating a 1-inch pipe that previously ran across the basement floor.
Financial Caps
The following table outlines the budget caps for the wastewater treatment plant (WWTP), including contract totals, previous balances, spending for the current month, and remaining balances.
| Category | Contract Total per Year | Previous Balance | Total Spent this Month | Remaining Balance |
|---|---|---|---|---|
| Maintenance Cap | $26,664. 12 | $21,832. 84 | $3,137. 00 | $18,695. 84 |
| Sludge Cap | $85,325. 04 | $70,375. 72 | $7,375. 75 | $62,999. 97 |
| Chemical Cap | $23,890. 92 | $19,085. 58 | $3,726. 66 | $15,358. 92 |
Health & Safety
- Incidents: There were no accidents in March.
- Safety Record: Personnel have worked 2,280 days (6 years and 4 months) without an accident or injury.
- Training: Inframark conducted weekly tailgate meetings, safety flash reports, and process control meetings.
Personnel
The report lists the following staff members and their operator certifications:
- Randy Lauer (Operator II): PA Class A, E; Wastewater Subclass 1,2,3,4
- Kyle Smiley (Operator III): PA Class A, E; Water Subclass 1,10,11,12; Wastewater Subclass 1
- Tony Perott (Operator I): PA Class C, E; Water Subclass 1,6,7,8,12
- Shawn Jones (Mechanic II): NA
- Joseph Pompa (Operator in Training): Training for PA DEP exam
- Luke Byrne (Project Manager): PA Class A, E; Water Subclass 1,7,8,10,11,12; Wastewater
On the Radar
Items currently being monitored or planned for future action include:
- SCADA programming
- Lawn repairs
- Influent splitter box lid repair
- SBR #2 air valve (follow-up)
- Lighting